JUNXY series pure resistive load bank is a safe and simple way to provide loading test, commissioning test, aging test, acceptance test for UPS, generator, AC voltage regulator, transformer, PV inverter, EV charger, AC & DC converter, battery bank, rectifier, energy storage system, PDU & many more AC & DC source. Such AC & DC source must be load bank commissioning verified before they could be used for the entire backup power system, make sure the backup power system runs perfectly in case of any downtime.
Load bank types:The pure resistive load bank includes 2 load types regarding its load voltage types: pure resistive 1phase & 3phase AC load bank & pure resistive DC load bank. Vertical cooling load bank or horizontal cooling load bank, outdoor type load bank and indoor type load bank designed according to the test site condition. The 3phase AC load bank could be by star connection or delta connection regarding the 3phase resistors connection configuration.
The pure resistive AC load bank outputs active load power only without the reactive power, The pure resistive AC load bank is capable to go by 3phase balance & unbalance loading test which meets clients’ different testing purpose. Load bank full power on/off is also a key function to test the power source on/off heavy load capability.
The pure resistive AC load bank digital meter testing each phase voltage, current, active power, power factor, reactive power & apparent power. The load bank load voltage & load current detected by the digital meter, and if the voltage & current exceed the preset value, the load bank digital meter will convert its NO contact to NC contact, activate the protection diagram, indicate over voltage/current alarm & protection with load removed automatically. A temperature sensor is also needed in case of load bank over temperature loading, to make sure the control system contactor, PLC, relay and its conducting wires always working in a good temperature condition.
It is very important to make sure fan always work normally to cool huge heat during loading test, so a digital meter to detect fan working voltage & current is needed. Alarm & load removed protection activated as soon as load bank fan low current and over voltage running.
Load bank fuse and circuit breaker protection is also essential for each load step, could provide the over current protection if any short circuit happens
Load bank control modesThe load bank has 2 control modes: either by local panel control or PC software remote control, 2 modes interlocked. The load bank communication by RS232, RS485, LAN, CAN. JUNXY series AC/DC load bank remote control communication protocol would be provided for clients’ integrating the load bank into the ATE system.
The 120/240V 50KW load bank is for split phase inverter load test, easy to use and over current/voltage protection
The load bank is designed for the AC120V & AC240V 2phase 3wires split phase inverter load test. Include the pure resistive, pure inductive and pure capacitive loading or combination loading. Power factor adjustable. 2 control modes: local panel by push buttons & PC software remote control
JUNXY offers you whole AC/DC load bank testing solutions of predictive failure analysis for UPS(uninterrupted power supply), generator, transformers, PV system, inverter etc, to validate the condition and output of such power systems comprehensively. Integrated AC/DC load bank could be made in one unit or separately with different load voltages as per your need for different applications.
Technical Specifications | |
Model | JUNXY-AC120V&AC240V-100KW-R Resistive AC Load Bank |
Load Element |
Stainless steel resistors |
Load Voltage | Split-Phase: AC240V 2phase 3wires(L1/N/L2) AC120V(L1-N), AC120V(L2-N), NOTE: Over voltage loading is PROHIBITED |
Load Power | Resistive: 50KW for AC120V 1phase 2wire, 60Hz(2 channel)
Resistive: 100KW for AC240V 2phase 2wire, 50Hz |
Load Steps | Load channel 1 @AC120V:
50W*2, 100W, 300W, 500W, 1KW, 2KW*2, 4KW, 10KW*2, 20KW Load channel 2 @AC120V: 50W*2, 100W, 300W, 500W, 1KW, 2KW*2, 4KW, 10KW*2, 20KW Load channel 3 @AC240V(channel 1 & 2 combined): 100W*2, 200W, 600W, 1KW, 2KW, 4KW*2, 8KW, 20KW*2, 40KW |
Power Factor | PF=1.0 |
Load Accuracy | ±5% |
Digital Meter | Voltage, Current, Power, Frequency, Power Factor and etc. |
Power Supply | 220V 50Hz, single phase |
Control Mode | 1. Manual control by push button
2. Remote control by PC software(OPTIONAL) |
Wire Connections | Copper bus bar for wire connections |
Insulation Class | F |
Protection Level | IP20(indoor use) |
Fan Noise | 75dB |
Cooling Mode | Force-air cooling |
Work Mode | Continuous work |
Protections | Overheating/buzzer alarm, overheating/over voltage protection, emergency stop button |
Ambient Temperature | -10℃~+50℃ |
Dimension | 600*850*1300mm |
Weight | 150KG |
Mobility | Four wheels |
Humidity | ≤95% |
Altitude | ≤2500 meters |