JUNXY series RCD load banks are similar to a reactive load bank in rating and purpose, except that leading power factor loads are created. The RCD load banks are used to simulate the no-linear or electronic loads typically for the industries: telecommunication, computer, UPS, generator & invertor, to test the real load capacity & crest factor.
Technical Specifications | |
---|---|
Model | JUNXY-AC600V-25KW-RCD AC Load Bank |
Load Element | Alloy resistors & Capacitors |
Load Voltage | AC600V 3phase 4wire, 50Hz (Phase voltage AC346.4V, line voltage AC600V) |
Rated Power | Diode rectifier with resistive load(R Load): 25KW@AC600V 3P4W 50Hz Diode rectifier with resistive & capacitive load(RCD): 25KVA@AC600V 3P4W 50Hz |
Rs Load Steps | Load steps for phase A/B/C: 0.2Ω, 0.4Ω, 0.8Ω, 1Ω, 2Ω, 4Ω, 8Ω, 15Ω Note: Rs are in parallel connection, and Rs steps are used to adjust the power factor |
Rs Load Steps MCB | Rs load steps MCB(mini circuit breaker)for phase A/B/C: 0.2Ω(10A), 0.4Ω(10A), 0.8Ω(10A), 1Ω(10A), 2Ω(20A), 4Ω(20A), 8Ω(32A), 15Ω(32A) Note: The MCB are used for Rs over current/load protection |
R/RCD Load Steps | Load steps for phase A/B/C: 0.1KW, 0.2KW, 0.4KW, 0.7KW, 1KW, 2KW, 4KW (Each phase 0.1KW-8.4KW adjustable @AC346.4V 1P2W, 50Hz) Note: 3 phases in parallel connection to load 25.2KW@AC346.4V |
Power Factor | PF=0.6 to 1.0 adjustable |
Load Accuracy | ±5% |
Digital Meter | Voltage, Current, Power, Frequency, Power Factor and etc. |
Power Supply | 230V 50Hz, single phase |
Control Mode | 1. Manual control by push buttons 2. Remote control by PC software |
Wire Connections | Copper bus bar for wire connections |
Insulation Class | F |
Protection Level | IP20(indoor use) |
Fan Noise | 75dB |
Cooling Mode | Force-air cooling |
Work Mode | Continuous work |
Protections | Over voltage/current/temperature alarm & protection, emergency stop button |
Ambient Temperature | -10℃~+50℃ |
Dimension | 700*1000*1560mm |
Weight | 218KG |
Mobility | Four wheels & lifting eyes |
Humidity | ≤95% |
Altitude | ≤2500 meters |