JUNXY AC415V 80KW Rack Mounted AC Load Bank

×

Why need load bank testing

It is really critical to ensure that your standby power supply system say UPS(uninterrupted power supply), battery bank, generator, transformers, inverter etc which especially located in harsh, dusty or corrosive environment working in good condition, when you need them most, if switched to be loaded when the main power supply in maintenance procedure or stop abnormally.

Such power supply systems could fail without proper preventative maintenance. JUNXY provides a whole range of custom preventative maintenance products solutions for your UPS systems, generators and many more to ensure constant uptime for your power systems and make you prepared for anything. Downtime could also be reduced by regular maintenance and thorough inspections which are the key to power supply systems maintenance.

JUNXY AC load banks could help highlight a large range of faults on the power supply systems it test. The first goal achieved when testing with JUNXY AC load bank is to ensure your power supply system is reliable or not by validating the power systems’ outputs to its technical specifications. The underlying question that JUNXY series AC load bank could answer you is--“how is my power supply systems constant uptime(technical performance) ?” The load bank also tests that the power supply system is not faulty, no faults in construction and components reliable, that the aging of the power supply system is in line with expectations and that there are no pending breakdowns or early signs of wear and tear.

JUNXY series AC load bank testing offers you whole solutions of predictive failure analysis for UPS(uninterrupted power supply), generator, transformers, PV system, inverter etc, to validate the condition and output of such power systems comprehensively. Integrated AC & DC load bank could be made in one unit or separately with different load voltages as per your need for different applications. Our solutions includes (click to view more):

  • RCD AC Load Bank(RCD)
  • Pure Resistive AC Load Bank(R)
  • Rack Mounted AC/DC Load Bank
  • Resistive and Inductive AC Load Bank(RL)
  • Resistive, Inductive and Capacitive AC Load Bank(RLC)
About JUNXY load banks resistor

Highly reliable and durable new alloy resistor is used for the JUNXY’s AC & DC load bank. It is thermal shrinkable and seal installed in the stainless steel pipe, whose surface with insulated heat sink. The resistor is moisture-proof, anti-corrosion, good heat dissipation, high insulation resistance, safe and reliable.

JUNXY load bank control modes

Two control modes available for JUNXY AC load banks: The local panel control mode and the remote control mode by PLC through PC software. Local control mode will be locked once load bank is switched to remote control mode. By applying the PLC, we could make load bank an intelligent test system, load power curve could be preset through PC software and all electrical parameters of EUT(equipment under test) including current, voltage, apparent power, active power, reactive power, power factor, frequency and warning info could be achieved automatically by the PC software and displayed by load bank digital meter. Up to 15 load banks at most could be parallel controlled by PC software which generating the test tables, curves and standard test report.

JUNXY-AC415V-20KW-R箱体模型0608.jpg
Technical Specifications
ModelJUNXY-AC415V-80KW-4CH Resistive AC Load Bank
Load ElementStainless steel resistors
Load VoltageAC415V 3Phase 5Wire, 50/60Hz
Load Power80KW for AC415V 3Phase 5Wire
Load Channel4 set independent removable 8U size 20KW rack mounted load bank

(Each rack load bank with 2 front handle & 1 rear handle)
Load Steps

Per Load Bank
Each rack mounted load bank with same load steps:

1KW, 2KW*2, 5KW, 10KW@AC415V 3P5W (1-20KW adjustable)
Power FactorPF=1
Load Accuracy±5%
Digital MeterNot available
Power SupplyAC240V 1phase 2wire 50/60Hz from test source directly
Control ModeManual control by MCB
Wire ConnectionsEach rack load bank with its own 5P(L1/L2/L3/N/GND) terminals for load input connections
Insulation ClassF
Fan Noise75dB
Cooling ModeForce-air horizontal cooling

(cool air inlet by front & side panel, hot air outlet by rear panel)

Each rack load bank fan air volume: 2000 CMH
Work ModeContinuous work
ProtectionsOver voltage/current/heat alarm & load removed automatically, emergency stop button
Ambient Temperature-10℃~+50℃
Dimension600*859*1811(W*D*H)
WeightAround 250KG
Mobility4 white color wheels
Humidity≤95%
Altitude≤2500 meters