JUNXY-AC380V-60KW-RCD Non-linear AC Load Bank

×

JUNXY series RCD load banks are similar to a reactive load bank in rating and purpose, except that leading power factor loads are created. The RCD load banks are used to simulate the no-linear or electronic loads typically for the industries: telecommunication, computer, UPS, generator & invertor, to test the real load capacity & crest factor.

Technical Specifications
ModelJUNXY-AC380V-60KW-RCD AC Load Bank
Load ElementAlloy resistors & Capacitors
Load VoltageAC380V 3phase 4wire, 50Hz

(Phase voltage AC220V, line voltage AC380V)
Rated PowerDiode rectifier with resistive load(R Load):

60KW@AC380V 3P4W 50Hz

Diode rectifier with resistive & capacitive load(RCD):

60KVA@AC380V 3P4W 50Hz
Rs Load StepsLoad steps for phase A/B/C:

0.1Ω, 0.2Ω, 0.4Ω, 0.8Ω, 1Ω, 2Ω, 4Ω, 8Ω, 15Ω

Note: Rs are in parallel connection, and Rs steps are used to adjust the power factor
R/RCD

Load Steps
Load steps for phase A/B/C:

0.2KW, 0.3KW, 0.5KW, 1KW, 2KW*2, 4KW, 5KW*2

(Each phase 0.2KW-20KW adjustable @AC220V 1P2W, 50Hz)
Power FactorPF=0.6 to 1.0 adjustable
Load Accuracy±5%
Digital MeterVoltage, Current, Power, Frequency, Power Factor and etc.
Power Supply230V 50Hz, single phase
Control ModeManual control by MCB
Wire ConnectionsCopper bus bar for wire connections
Insulation ClassF
Protection LevelIP20(indoor use)
Fan Noise75dB
Cooling ModeForce-air cooling
Work ModeContinuous work
ProtectionsOver voltage/current/temperature alarm & protection, emergency stop button
Ambient Temperature-10℃~+50℃
Dimension750*1000*1400mm
Weight218KG
MobilityFour wheels
Humidity≤95%
Altitude≤2500 meters