JUNXY-AC380V-500KW-RL Resistive, Inductive AC Load Bank

×

Why need load bank testing

It is really critical that your standby power system say UPS(uninterrupted power supply), battery bank, generator, transformers, inverter etc working in good condition if switched to be loaded when the main power supply in maintenance procedure or stop abnormally. Downtime could be reduced by regular maintenance and thorough inspections which are the key to power supply systems maintenance.

Critical power backup equipment like UPS System and generator which especially located in harsh, dusty or corrosive environment will fail without proper preventative maintenance. JUNXY provides a whole range of custom preventative maintenance products solutions for UPS systems and generators and many more to ensure constant uptime for your power systems and make you prepared for anything.

Load banks help highlight a large range of faults on the equipment it tests. The first objective when testing with an electric bank is to ensure your equipment’s power supply is reliable. The underlying question that needs answering is whether your equipment will have sufficient power supply to ensure uninterrupted operational performance. The load bank also tests that the equipment is not faulty, that there are no faults in construction, that the aging of the equipment is in line with expectations, that the components are reliable and that there are no pending breakdowns or early signs of wear and tear. The load bank also ensures that the product delivers power conform to its specification.

Resistive & reactive load banks are able mimic motor loads and electromagnetic devices within a power system as well as purely resistive loads by offering the ability to set a specific power factor (pf). Many backup generators and turbines are rated at 0.7, 0.8 or 0.85 power factor and need to be commissioned at nameplate capacity using a combination of resistive and reactive load to fully qualify their operating capability. Using a resistive & reactive load bank enables comprehensive testing from a single unit. JUNXY has an extensive range of resistive & reactive load banks to simulate these types of loads on a power source and the transformers, relays, and switches which will distribute the power throughout your facility.

Inductive & capacitive load banks are reactive only and must be used in combination with a resistive load bank to provide the desired load profile to test a power system. Reactive loads banks can provide either a leading power factor (Capacitive) or lagging power factor (Inductive).

JUNXY series AC load bank testing offers you whole solutions of predictive failure analysis for UPS(uninterrupted power supply), generator, transformers, PV system, inverter etc, to validate the condition and output of such power systems comprehensively, which includes (click to view more):

Technical Specifications
ModelJUNXY-AC380V-500KW-RL AC Load Bank
Load ElementResistor, inductor
Load VoltageAC380V 3P4W
Frequency50Hz
Load PowerR: 500KW(3phase taotal power)

L: 300KVar(3phase taotal power)
Load StepsResistive Load Steps (three phase controlled):

1KW, 2KW, 2KW, 5KW, 10KW*4, 20KW*5, 50KW, 100KW*4

Inductive Load Steps (three phase controlled):

0.6KVar, 1.2KVar, 1.2KVar, 3KVar, 6KVar*4, 12KVar*5, 30KVar, 60KVar*3
Power FactorPF adjustable by resistive & inductive combined
Load AccuracyResistor: ±5%, Inductor: ±10%
Digital Metervoltage, current, active power, reactive power, apparent power, power factor, energy, frequency
Mains Voltage220V 50Hz, single phase
2 Control Modes
1. Local control panel by push buttons

2. PC software remote control
Load Input

Wire Connections
Copper bus bar for wire connections
Insulation ClassF
Protection LevelIP20(indoor use)
Fan Noise75dB
Cooling ModeForce-air vertical cooling, by axial-flow fans.
Work ModeContinuous work
ProtectionsOverheating/Buzzer alarm, Overheating/Over current, over voltage, over load protection, emergency stop button
Dimension1100*1370*1900mm(W*D*H) 1100*1370*1500mm(W*D*H)
WeightAround 2T
Ambient Temperature-10℃~+50℃
MobilityStationary by forklift pocket
Humidity≤95%
Altitude≤2500 meters