JUNXY AC300V 150A ATS load current simulation RL load bank

×

Why load bank testing is important?

JUNXY series AC/DC load banks are for many power supplies load bank testing, to ensure that the standby power supply system say UPS(uninterrupted power supply), battery bank, generator, transformers, inverter etc which especially located in harsh, dusty or corrosive environment working in good condition, when you need them most, if switched to be loaded when the main power supply in maintenance procedure or stop abnormally.

The AC/DC load bank loading test preventative maintenance of such power supply systems could free you from power supply failure, to ensure constant uptime for your power systems and make you prepared for anything. Downtime could also be reduced by regular maintenance and thorough inspections which are the key to power supply systems maintenance.

Load bank testing could help highlight a large range of faults on the power supply systems it test. The first goal achieved when testing with JUNXY AC/DC load bank is to ensure your power supply system is reliable or not by validating the power systems’ outputs to its technical specifications. The underlying question that JUNXY series AC/DC load bank could answer you is--“how is my power supply systems constant uptime(technical performance) ?” The load bank also tests that the power supply system is not faulty, no faults in construction and components reliable, that the aging of the power supply system is in line with expectations and that there are no pending breakdowns or early signs of wear and tear.

The ATS load bank could do adjustable load current/voltage/power factor to achieve the ATS testing goal.


Technical Specifications
Model JUNXY-AC300V-150A-RL Resistive & Inductive AC Load Bank
Load Element Stainless steel resistors & Inductors.
Load Voltage AC100V-AC300V 1phase, 50Hz
Load Steps
@AC100-AC300V
8 Resistive Load Steps(ohm):
0.5ohm 1ohm 2ohm
4ohm 8ohm 16ohm
32ohm 32ohm+50ohm rheostat
8 Inductive Load Steps(mH):
0.3125mH 0.625mH
1.25mH 2.5mH
5mH 10mH
20mH 40mH
Power Factor PF adjustable
Load Accuracy Resistor/Inductor: ±5%
Digital Meter Voltage, Current, Power, Frequency, Power Factor and etc.
Power Supply 230V 50Hz, single phase
Control Mode 1. Manual control by push button
2. Remote control by PC software
Load Elements
Connections
1. All resistors in parallel connection.
(each resistor in series connection with one contactor)
2. All inductors in series connection.
(each inductor in parallel connection with one contactor. One contactor shorting all inductors)
3. Then resistors in series connection with inductors
Digital Meter or units can be specified by customer
Insulation Class F
Protection Level IP20(indoor use)
Fan Noise 75dB
Cooling Mode Force-air cooling: vertical cooling
Duty Cycle 1. Max 17% duty cycle
(10 seconds ON then 50 seconds OFF per minute)
2. 100% duty cycle
(if load current not exceed 1/3 of R&L rated current)