Inductive & capacitive AC load banks are reactive only and must be used in combination with a resistive load bank to provide the desired load profile to test a power system. Reactive loads banks can provide either a leading power factor (Capacitive) or lagging power factor (Inductive).
Islanding effect is not allowed in the solar photovoltaic power system regarding the power quality and electrical safety, since it will cause potential threat and damage to the electrical equipments. JUNXY inverter RLC load banks are mostly used for inverter anti-islanding preventative test experiments which meets the PV & grid inverter testing requirements for islanding prevention detection, work efficiency test, overload protection test, over current protection test, power factor test, grid current harmonic test, resonance point test, and so on. PV Transformer and battery system maintenance should also be included for Grid-connected photovoltaic power plant operation and maintenance by JUNXY products solutions.
JUNXY series AC load bank testing offers you whole solutions of predictive failure analysis for UPS(uninterrupted power supply), generator, transformers, PV system, inverter etc, to validate the condition and output of such power systems comprehensively, which includes (click to view more):
JUNXY resistive & reactive RLC load bank, labview PC software, outdoor type design with each phase independently controlled. power factor adjustable, suitable for inverter loading test. The 851KW/851KVar load bank is a hihg power RLC resistive & reactive load bank, software develop by labview, outdoor type design with each phase independently controlled. power factor adjustable, suitable for inverter loading test.
Technical Specifications | |
---|---|
Model | JUNXY-AC800V-851KW-RLC AC Load Bank |
Load Element | Resistor, inductor and capacitor |
Load Voltage | AC800V 3P4W & AC461.9V 1P2W (3P3W loading prohibited) |
Rated Frequency | 50/60Hz |
3 Phase Load Power | R=851KW(283KW per phase @AC461.9V 50/60Hz) L=1021KVar(340KVar per phase @AC461.9V 50Hz) C=1021KVar(340KVar per phase @AC461.9V 60Hz) |
Load Steps Per Phase | Customized made |
Power Factor | Leading and lagging power factor 0-1.0 adjustable |
Load Accuracy | Resistor/capacitor: ±5%, Inductor: ±10% |
Digital Meter | voltage, current, active power, reactive power, apparent power, power factor, energy, frequency |
Mains Voltage | AC400V 3P5W 50Hz by quick connector Pls prepare wire by suitable length with minimum 6 mm² |
Control Modes | 1. Local control panel 2. PC remote control |
Load Input Wire Connections | Copper bus bar for wire connections |
Insulation Class | F |
Protection Level | IP54(outdoor usage) |