Following on from construction and testing, Data Centre Commissioning is essential to ensure that the completed facility is configured for maximum efficiency. Missing out the essential Data Centre Commissioning can lead to an inefficient facility and higher than expected operational costs. By simply identifying where equipment manufacturers’ standard specifications are not appropriate for the IT load, the supporting infrastructure, in particular the cooling plant, can be configured to meet the requirements of the facility and lead to much higher levels of efficiency. Data centre commissioning can lead to significant energy savings when implemented correctly by a specialist commissioning team. By engaging JUNXY power solutions to ensure that systems are running correctly, clients have saved up to 67% on facility operational costs.
The Junxy rack mounted AC & DC load banks are designed especially for internet data center (IDC) test and commissioning. Load bank integrated system test (IST) could precisely simulate the data center’s electricity consumption, heat dissipation, air flow, hot & cold aisle testing, thus to ensure the effective operation of power supply & distribution system (generator, UPS, EPS included), air conditioning system, lightning protection and earthing system, monitoring system, data center integrated environments, cabinet IT environment, providing independent verification of integrated system testing. Successful IST(integrated system test) should have installation of server load banks in data center and server room etc, Junxy provides resistive, reactive and capacitive load banks in low or medium voltage to cover the entire scope of your commission and testing requirements.
Applications
Technical Specifications | |
---|---|
Model | JUNXY-AC230V-6.6KW-R Resistive AC Load Bank |
Load Element | Stainless steel resistor |
Load Voltage | AC230V single phase, 50/60Hz |
Rated Power | 6.6KW@AC230V |
Feeds Quantity | Dual feeds, interlock by switch selectable POWER1(Feed 1): AC11, AC12, AC13 POWER2(Feed 2): AC21, AC22, AC23 |
Load Steps | 3 independent load channels per feed: AC11(AC21) Load Channel (Fan power supply also): 2*1.1KW AC12(AC22) Load Channel: 2*1.1KW AC13(AC23) Load Channel: 2*1.1KW Total 6 load steps: 1.1KW*6 |
Power Factor | PF=1 |
Load Accuracy | ±5% |
Power Supply | Fan activated by AC11(AC21) cable: 230V 1phase 50Hz from test source |
Control Mode | Manual control by mini circuit breaker |
Insulation Class | F |
Protection Level | IP20(indoor use) |
Fan Noise | 75dB |
Cooling Mode | Fan force-air cooling, powered from the test source. Cool air intake at front, hot air exhaust at rear. Fan activated by AC11(AC21): 230V 1phase 50Hz from test source |
Work Mode | Continuous work |
Ambient Temperature | -10℃~+50℃ |
Load Input Cables | Six C19-C20 cables |
Dimension | 4U 19 inch rack, depth 600mm |
Weight | 22KG |
Mobility | Two front handles and one rear handle |
Humidity | ≤95% |
Altitude | ≤2500 meters |
1. One Load Bank Main Unit.
2. Six C19-C20 cables