Dual Feed AC230V 6.6KW Rack Type Load Bank For Data Center Server Simulation

×

JUNXY Rack Mounted Load Bank:

Pls click here to view the video for the data center commissioning loading test by JUNXY 230V 6.6KW data center server simulator load bank.

Following on from construction and testing, Data Centre Commissioning is essential to ensure that the completed facility is configured for maximum efficiency. Missing out the essential Data Centre Commissioning can lead to an inefficient facility and higher than expected operational costs. By simply identifying where equipment manufacturers’ standard specifications are not appropriate for the IT load, the supporting infrastructure, in particular the cooling plant, can be configured to meet the requirements of the facility and lead to much higher levels of efficiency. Data centre commissioning can lead to significant energy savings when implemented correctly by a specialist commissioning team. By engaging JUNXY power solutions to ensure that systems are running correctly, clients have saved up to 67% on facility operational costs.

The Junxy rack mounted AC & DC load banks are designed especially for internet data center (IDC) test and commissioning. Load bank integrated system test (IST) could precisely simulate the data center’s electricity consumption, heat dissipation, air flow, hot & cold aisle testing, thus to ensure the effective operation of power supply & distribution system (generator, UPS, EPS included), air conditioning system, lightning protection and earthing system, monitoring system, data center integrated environments, cabinet IT environment, providing independent verification of integrated system testing. Successful IST(integrated system test) should have installation of server load banks in data center and server room etc, Junxy provides resistive, reactive and capacitive load banks in low or medium voltage to cover the entire scope of your commission and testing requirements.

Applications
  • Data center & server room cooling system test
  • Data center air flow, hot/cold aisle environment inspection
  • Validating the tire level of data center
  • Validating the reliability of data center power supply & distribution system
  • Testing the main network before connecting user devices (servers, switches, etc.)
JUNXY-6.6KW-AUTO-1-scaled.jpg

Technical Specifications
ModelJUNXY-AC230V-6.6KW-R Resistive AC Load Bank
Load ElementStainless steel resistor
Load VoltageAC230V single phase, 50/60Hz
Rated Power6.6KW@AC230V
Feeds QuantityDual feeds, interlock by switch selectable

POWER1(Feed 1): AC11, AC12, AC13

POWER2(Feed 2): AC21, AC22, AC23
Load Steps
3 independent load channels per feed:

AC11(AC21) Load Channel (Fan power supply also): 2*1.1KW

AC12(AC22) Load Channel: 2*1.1KW

AC13(AC23) Load Channel: 2*1.1KW

Total 6 load steps: 1.1KW*6
Power FactorPF=1
Load Accuracy±5%
Power SupplyFan activated by AC11(AC21) cable:

230V 1phase 50Hz from test source
Control ModeManual control by mini circuit breaker
Insulation ClassF
Protection LevelIP20(indoor use)
Fan Noise75dB
Cooling ModeFan force-air cooling, powered from the test source.

Cool air intake at front, hot air exhaust at rear.

Fan activated by AC11(AC21): 230V 1phase 50Hz from test source
Work ModeContinuous work
Ambient Temperature-10℃~+50℃
Load Input CablesSix C19-C20 cables
Dimension4U 19 inch rack, depth 600mm
Weight22KG
MobilityTwo front handles and one rear handle
Humidity≤95%
Altitude≤2500 meters

NOTE: Each load bank includes the standard items:

1. One Load Bank Main Unit.

2. Six C19-C20 cables