JUNXY-DC300V/600V/1000V-100KW-R Resistive DC Load Bank EV Charger Load Tester

×

Why load bank testing is important?

JUNXY series AC/DC load banks are for many power supplies load bank testing, to ensure that the standby power supply system say UPS(uninterrupted power supply), battery bank, generator, transformers, inverter etc which especially located in harsh, dusty or corrosive environment working in good condition, when you need them most, if switched to be loaded when the main power supply in maintenance procedure or stop abnormally.

The AC/DC load bank loading test preventative maintenance of such power supply systems could free you from power supply failure, to ensure constant uptime for your power systems and make you prepared for anything. Downtime could also be reduced by regular maintenance and thorough inspections which are the key to power supply systems maintenance.

Load bank testing could help highlight a large range of faults on the power supply systems it test. The first goal achieved when testing with JUNXY AC/DC load bank is to ensure your power supply system is reliable or not by validating the power systems’ outputs to its technical specifications. The underlying question that JUNXY series AC/DC load bank could answer you is--“how is my power supply systems constant uptime(technical performance) ?” The load bank also tests that the power supply system is not faulty, no faults in construction and components reliable, that the aging of the power supply system is in line with expectations and that there are no pending breakdowns or early signs of wear and tear.

JUNXY offers you whole AC/DC load bank testing solutions of predictive failure analysis for UPS(uninterrupted power supply), generator, transformers, PV system, inverter etc, to validate the condition and output of such power systems comprehensively. Integrated AC/DC load bank could be made in one unit or separately with different load voltages as per your need for different applications.

DC300V600V1000V-100KW-load-bank-2-scaled.jpg
Technical Specifications
ModelJUNXY-AC300V/600V/1000V-100KW-R Resistive DC Load Bank
Load ElementStainless steel resistors
Rated VoltageDC300V, DC600V, DC1000V
Rated Power100KW@DC300V,
100KW@DC600V,
100KW@DC1000V
Load Steps10KW, 10KW, 20KW, 30KW, 30KW
(10W-100KW adjustable @DC300V/DC600V/DC1000V)

Power FactorPF=1.0
Load Accuracy±5%
Digital MeterVoltage, Current, Power
Power Supply230V 50Hz, single phase
Control Modes1. Local panel by touch screen
2. GPIO DC5V control by terminals

3. Relay DC24V coils control by terminals

4. Software developed by FST through RS485 cable

5. Software developed by client through CAN
Load Input
1. Copper bus bar

2. CCS2 connector(DO NOT exceed DC1000V & 200A)

3. Chademo connector(DO NOT exceed DC600V & 200A)
Insulation ClassF
Protection LevelIP20(indoor use)
Fan Noise75dB
Cooling ModeForce-air vertical cooling
Work ModeContinuous work
ProtectionsOver voltage/current/temperature alarm & load removed automatically, emergency stop button
Ambient Temperature-10℃~+50℃
Dimension

800*950*1850mm
Weight190KG
MobilityFour wheels & lifting eyes
Humidity≤95%
Altitude≤2500 meters